1.2V 200Ah Nickel Cadmium Rechargeable Battery For Emergency Lighting UPS Battery
Product Details:
| Place of Origin: | China |
| Certification: | CB CE UN38.3 MSDS |
| Model Number: | 1.2V 200Ah |
Payment & Shipping Terms:
| Minimum Order Quantity: | 1000PCS |
|---|---|
| Packaging Details: | Industrial Pakcage |
| Delivery Time: | 35 working days |
| Payment Terms: | L/C,T/T,Western Union |
|
Detail Information |
|||
| Battery Type: | Nicd Battery Pack Ups | Capacity: | 200Ah |
|---|---|---|---|
| Voltage: | 1.2V | Dimension: | L:105 W: 165 H:345 |
| Weight: | 10.5kg | Discharge Cut-off Voltage: | 1.0V |
| Self-Discharge Rate: | 10-15% Per Month | Guarantee: | Three Years |
| Highlight: | 1.2 V Nicd Rechargeable Battery,200Ah Nickel Cadmium Rechargeable Battery,12v Nickel Cadmium Rechargeable Battery |
||
Product Description
1.2V 200Ah nickel cadmium rechargeable battery for Emergency lighting UPS battery
Features
- Exceptional Cycle Life: 2000+ deep discharge cycles
-
Wide Temperature Operation: Performs from -40°C to +50°C
-
High Reliability: Proven technology for critical applications
-
Overcharge Tolerance: Withstands continuous overcharge
-
Deep Discharge Recovery: Full recovery from complete discharge
-
Low Maintenance: Minimal watering requirements
-
Long Service Life: 15-20 years design life
-
High Rate Capability: Supports high current discharges
Specification
| Normal Voltage | 1.2V |
| Capacity | 200Ah |
| Weight | With Electrolyte: 10.0kg/22.0lbs Without Electrolyte: 7.8kg/17.2lbs |
| Dimensions | L:105/4.1 W:165/6.5 H:345/13.6 (mm/inch) |
| Operating Teerature Range | -20°C to + 60°C(-4°F to +140°F) |
| Cycle Life | ≥2000 cycles (to 80% capacity) |
| Design Life | 15-20 years |
| Self-Discharge Rate | 10-15% per month |
| Standard Charge Current | 0.1C (20A) for 7-8 hours |
| Max Discharge Current | 5C (1000A) for 30 seconds |
| Discharge Cut-off Voltage | 1.0V |
| Internal Resistance | ≤0.1mΩ |
![]()
Applications
- Emergency Lighting Systems: Exit signs, emergency luminaires
-
UPS Systems: Uninterruptible power supplies for critical infrastructure
-
Telecommunications: Base station backup power
-
Security Systems: Alarm and access control systems
-
Medical Equipment: Emergency medical device backup
-
Industrial Control Systems: Process control backup power
-
Railway Signaling: Signaling system backup power
Warnings & Precautions
Charging Precautions
- Use NiCd-specific chargers with temperature compensation
-
Maintain float voltage at 1.40-1.45V per cell at 20°C
-
Perform equalization charges monthly at 1.50-1.55V per cell
-
Monitor temperature during charging - reduce voltage at higher temperatures
-
Never exceed 1.65V per cell under any conditions
Electrolyte Handling
- Wear appropriate PPE: acid-resistant gloves, goggles, and apron
-
Use only distilled or demineralized water for topping up
-
Maintain electrolyte level above plates but below maximum mark
-
Never add acid to electrolyte - only add water
-
Clean any electrolyte spills immediately with bicarbonate solution
Discharging Precautions
- Avoid continuous discharge below 1.0V per cell
-
Limit maximum discharge current to 5C (1000A) for 30 seconds maximum
-
Monitor cell temperatures during high-rate discharges
-
Allow cooling between high-current discharge cycles
Storage & Handling
- Store in cool, dry, well-ventilated area
-
Keep away from direct sunlight and heat sources
-
Store upright to prevent electrolyte leakage
-
Keep terminals protected and insulated when not in use
-
Implement earthquake protection in seismic zones
Transportation
- Transport upright to prevent electrolyte leakage
-
Secure properly to prevent movement during transit
-
Comply with IATA DGR for air transport
-
Follow ADR/RID/IMDG regulations for ground/sea transport
-
Package as UN 2795, Battery, wet, filled with alkali


